---
title: "Why does my RCBO keep tripping? | NICEIC · From £65 an hour"
description: "RCBO keeps tripping in Eastleigh? MCI Electrical tests the circuit, finds the leak, overload or short and repairs what has failed. · Call 07366 896562"
canonical: "https://mci-electrical.co.uk/problems/rcbo-keeps-tripping"
---

# Why does my RCBO keep tripping?

> RCBO keeps tripping in Eastleigh? MCI Electrical tests the circuit, finds the leak, overload or short and repairs what has failed. · Call 07366 896562

An RCBO keeps tripping when its circuit leaks current to earth, carries too much load or has a short. MCI Electrical tests that circuit for Eastleigh workplaces and finds the part at fault.

## Why does an RCBO keep tripping?

An RCBO is a breaker in the consumer unit or distribution board that guards one circuit against overload, short circuit and earth leakage. It cuts only that circuit when it senses a fault.
- **Earth leakage from a connected item:** A kettle, heater, dryer or charger that leaks a little current to earth trips the leakage side of the RCBO. Several items on one circuit can add their small leaks together until the total crosses the limit.
- **Too much load on the circuit:** New heaters, tools or a machine added to a circuit can draw more current than the breaker is rated for. This kind of trip tends to come after a delay, when the load is at its peak, rather than the moment something is switched on.
- **A short circuit in the wiring or an item:** A short between live and neutral trips the RCBO at once, and a reset drops straight out again. Crushed cable, a burnt joint or a failed appliance can all cause it.
- **Damp in a fitting:** Moisture in an outdoor light, a wash area socket or a trunking joint lets current leak to earth. Trips that follow rain, jet washing or a cold, wet morning point to this cause.
- **A worn RCBO:** An RCBO that has aged can become oversensitive and trip on a healthy circuit. It is the last thing to suspect, once testing has cleared the cable and everything connected to it.

## What can I check safely when an RCBO trips?

Keep to the closed cabinet door and the plug sockets. None of these checks needs a cover off or a tool, and anything hot, scorched or smelling of burning stays untouched.
- **Read the label and the flag:** Find the lever that has dropped and read which circuit it serves. Many RCBOs show a small flag, and a leakage trip looks different from an overload trip, so note what you see.
- **Unplug the portable items:** Switch off and unplug kettles, chargers, heaters and extension leads on that circuit. Leave wired in equipment connected and do not open any of it.
- **Reset it once:** Push the lever fully down and then up, one time only. If it stays up, plug items back in one at a time, and the one that trips it again is the likely culprit.
- **Note when it trips:** Jot down the time, the weather and what was running. A trip the instant power returns and a trip after an hour of use point to different faults.

## When should I book an electrician for a tripping RCBO?

Book when the safe checks have not settled it, or straight away if there is heat or damage. A breaker that keeps returning to the off position is reporting a fault that is still on the circuit.
- **It trips with nothing plugged in:** With every portable item unplugged and the circuit still tripping, the fault is in the fixed wiring or a wired in fitting, which only test instruments can trace.
- **It will not stay up:** A lever that refuses to latch, or an RCBO that feels loose or cracked, needs testing before anyone uses that circuit again.
- **It keeps coming back:** A trip that returns after each reset, or every few days, means the cause has not gone away. Leave the circuit switched off until it is tested.
- **There is heat, a smell or damage:** Warm covers, brown marks, a burning smell or a cracked fitting call for the circuit to stay off and a visit as soon as it can be arranged.

## What happens when an electrician visits for a tripping RCBO?

The visit starts with the tripping circuit and works outwards, so each test removes one possible cause before the next.
- **We ask what happened:** We ask which areas lost power, what was running and whether the trips follow weather or a time of day. That history tells us whether to look first for leakage, overload or a short.
- **We isolate and test the circuit:** With the circuit switched off at the board, we take insulation resistance readings, which show whether current is leaking from the cable or an item, and loop impedance readings, which show how the circuit behaves under fault.
- **We check the fittings and the RCBO:** We look at sockets, lights and connections along the circuit for damp, damage or loose terminals, then test whether the RCBO itself operates as it should.
- **We repair, retest and record:** The failed part is put right and the circuit tested again before it is switched back on. If the circuit was altered, NICEIC paperwork follows, and you get a note of the cause.

## What affects the price of fixing a tripping RCBO?

The price card covers coming to the premises and testing the circuit that trips until the cause is found. Fault finding is charged by the hour, so the total follows how long the trace takes and how much of the circuit has to be checked.
- Commercial fault finding and repair: from £75 an hour
- A damp fitting found at the first look takes less time than a leak that only appears under load.
- A replacement RCBO, socket or length of cable is priced once testing shows what has failed.
- Quotes are free and there is no callout fee, so a repair can wait until you have seen the price.

## Electrical fault finding near you
- [Electrical fault finding in Chandler's Ford](https://mci-electrical.co.uk/commercial-electrician-chandlers-ford/commercial-fault-finding)
- [Electrical fault finding in Hedge End](https://mci-electrical.co.uk/commercial-electrician-hedge-end/commercial-fault-finding)
- [Electrical fault finding in Southampton](https://mci-electrical.co.uk/commercial-electrician-southampton/commercial-fault-finding)

## Questions about an RCBO that keeps tripping

### Can I just fit a new RCBO?

A new RCBO will usually trip for the same reason if the fault is still on the circuit. The device is doing its job, so testing the circuit first shows whether a replacement is needed at all. Work inside the consumer unit is for an electrician.

### Why does the RCBO only trip when it rains?

Rain points to water reaching an outdoor light, socket or cable on that circuit. The leak is small until the weather adds moisture. Note which outside equipment is on the circuit, keep it switched off and mention the pattern when you call.

### Will the whole building lose power while you test?

An RCBO guards one circuit, so only that circuit needs to be off for most of the testing. Other ways on the board stay live where the layout allows, and we tell you before anything else is switched off.

### Is it safe to leave a tripping circuit switched off?

Yes. An off circuit carries no current, and leaving it off is the safe choice while the fault is found. Do not tape, hold or wedge the lever to keep it up.

## Related problems
- [Circuit breaker keeps tripping](https://mci-electrical.co.uk/problems/circuit-breaker-keeps-tripping): A breaker that keeps tripping is either overloaded or protecting against a fault, and testing the circuit shows which.
- [Consumer unit tripping with nothing plugged in](https://mci-electrical.co.uk/problems/consumer-unit-tripping-nothing-plugged-in): A trip with nothing plugged in points to fixed wiring, lighting or wired in equipment, which needs testing one circuit at a time.
- [Cooker switch not working](https://mci-electrical.co.uk/problems/cooker-switch-not-working): Power to a cooker passes through a breaker, a wall switch and the appliance's own terminals, and a reading at each one shows where it stops.
- [Fuse keeps blowing](https://mci-electrical.co.uk/problems/fuse-keeps-blowing): Repeated blown fuses mean too much current, from an overload or a fault, and a test of the circuit shows which one.
- [Lights not working but sockets are fine](https://mci-electrical.co.uk/problems/lights-not-working-but-sockets-are): Sockets work because they run on separate circuits, so the fault is on the one lighting circuit that has stopped.
- [MCB keeps tripping in a commercial building](https://mci-electrical.co.uk/problems/mcb-keeps-tripping): A tripping MCB means its circuit is overloaded or has a fault, and testing outwards from the board shows which one and what has to change.

## Sources
- [Electrical Safety First: Safety Guidance](https://www.electricalsafetyfirst.org.uk/guidance/)
- [BS 7671: IET Wiring Regulations (18th Edition)](https://electrical.theiet.org/bs-7671/)
- [IET: BS 7671 Guidance Publications](https://electrical.theiet.org/guidance-and-codes-of-practice/publications-by-category/bs-7671-and-guidance/)

Updated 2026-11-20.

[Electrical fault finding](https://mci-electrical.co.uk/services/commercial-fault-finding)

## Book or ask a question
- [Book Now](https://mci-electrical.co.uk/#chat)
